[SD2110V]  Temperature and humidity sensor voltage output


SD2110V SD2110V

Technical Parameters

Technical parameterParameter value
BrandSONBEST
Temperature measuring range0~50℃/-20~80℃/-40~60℃
Temperature measuring accuracy±0.3℃ @25℃
Range change mode DIP switch
Humidity measuring range0~100%RH
Humidity accuracy±3%RH @25℃
Output InterfaceDC0~5V
PowerDC12~24V 1A
Running temperature-30~85℃
Working humidity5%RH~90%RH

Wiring instructions

Why choose this product?

SD2110V

Why choose this product?

SD2110V SD2110V

How to use?

SD2110V

Application solution

SD2110V

Product List

SD2110V

Pictures

SD2110V

1. temperature and DC0-5Vvoltage computing relationship

  The product comes standard with 0~50℃/-20~80℃/-40~60℃ multi-range. The default range is 0~50℃. Users can modify the range by dialing the switch. For example, the range is 0~50℃, the analog output is 0~5V DC0-5Vvoltage signal, temperature and DC0-5Vvoltage The calculation relationship is as shown in the formula: C = (A2-A1) * (X-B1) / (B2-B1) + A1, where A2 is temperature range upper limit, A1 is the lower limit of the range, B2 is DC0-5Vvoltage output range upper limit, B1 is the lower limit, X is the currently read temperature value, and C is the calculated DC0-5Vvoltage value. The list of commonly used values is as follows:
DC0-5Vvoltage(V)temperatureValue (℃) Calculation Process
00.0(50-0)*(0-0)÷(5-0)+0
110.0(50-0)*(1-0)÷(5-0)+0
220.0(50-0)*(2-0)÷(5-0)+0
330.0(50-0)*(3-0)÷(5-0)+0
440.0(50-0)*(4-0)÷(5-0)+0
550.0(50-0)*(5-0)÷(5-0)+0
    As shown in the above formula, when measuring 2.5V, current DC0-5Vvoltage is 25℃。

2. humidity and DC0-5Vvoltage computing relationship

  For example, the range is 0~100%RH, the analog output is 0~5V DC0-5Vvoltage signal, humidity and DC0-5Vvoltage The calculation relationship is as shown in the formula: C = (A2-A1) * (X-B1) / (B2-B1) + A1, where A2 is humidity range upper limit, A1 is the lower limit of the range, B2 is DC0-5Vvoltage output range upper limit, B1 is the lower limit, X is the currently read humidity value, and C is the calculated DC0-5Vvoltage value. The list of commonly used values is as follows:
DC0-5Vvoltage(V)humidityValue (%RH) Calculation Process
00.0(100-0)*(0-0)÷(5-0)+0
120.0(100-0)*(1-0)÷(5-0)+0
240.0(100-0)*(2-0)÷(5-0)+0
360.0(100-0)*(3-0)÷(5-0)+0
480.0(100-0)*(4-0)÷(5-0)+0
5100.0(100-0)*(5-0)÷(5-0)+0
    As shown in the above formula, when measuring 2.5V, current DC0-5Vvoltage is 50%RH。
software for test product
Setup Software
Development File

 Online shop 

 Contact Online 

Email: sale@sonbest.com

TYPE: SD2110V

WeChat: 13918126020

SKYPE: SOOBUU

Phone: 021-51083595

QQ1: 71182854 QQ2:613035997