[SD6070B]  Industrial protection with display dual beam infrared carbon dioxide sensor

SD6070B SD6070B

Technical Parameters

Technical parameterParameter value
BrandSONBEST
CO2 range0~5000ppm
CO2 accuracy±100ppm
Communication InterfaceRS485
Default baud rate9600 8 n 1
PowerDC9~24V 1A
Running temperature-30~85℃
Working humidity5%RH~90%RH

Product Size

SD6070B SD6070B SD6070B

Wiring instructions

Why choose this product?

SD6070B SD6070B

Why choose this product?

SD6070B SD6070B SD6070B

How to use?

SD6070B

Application solution

SD6070B

Product List

SD6070B

Pictures

SD6070B SD6070B SD6070B

Communication Protocol

    The product uses RS485 MODBUS-RTU standard protocol format, all operation or reply commands are hexadecimal data. The default device address is 1 when the device leaves the factory, and the module or NON-Recorder default baud rate is 9600,8,n,1 ,but data recorder default baud rate is 115200 .
1. Read data (function code 0x03)
    Inquiry frame (hexadecimal), sending example: query 1 data of 1# device, the upper computer sends the command: 01 03 00 00 00 01 84 0A .
Address Function Code Start Address Data Length Check Code
010300 0000 0184 0A
    For the correct query frame, the device will respond with data: 01 03 02 00 79 79 A6 , response format:
Address Function Code LengthData 1Check Code
0103 0200 79 79 A6
    Data description: The data in the command is hexadecimal, take data 1 as an example, 00 79 is converted to decimal value is 121, for general Sobo products, the temperature and humidity data magnification is 100, and the light data The magnification is 1 or 10. The data magnification of this product is 1, the real value is: 121/1=121, and so on.
2. Common data address table
Configuration Address Register Address Register Description Data Type Value Range
4000100 00carbon dioxideRead Only0~65535
4010100 64Model CodeRead/Write0~65535
4010200 65 total number of measuring points read/write 1~20
4010300 66device addressread/write1~249
4010400 67baud rateread/write0~6
4010500 68communication moderead/write1~4
4010600 69protocol typeread/write1~10