[SM3710M]  4-20mA current type duct type temperature and humidity sensor

SM3710M SM3710M
Technical parameterParameter value
BrandSONBEST
Temperature measuring range0~50℃/-20~80℃/-40~60℃
Temperature measuring accuracy±0.3℃ @25℃
Range change mode DIP switch
Humidity measuring range0~100%RH
Humidity accuracy±3%RH @25℃
Communication InterfaceDC4~20mA
PowerDC12~24V 1A
Running temperature-30~85℃
Working humidity5%RH~90%RH

Product Size

SM3710M

Wiring instructions

Why choose this product?

SM3710M SM3710M SM3710M SM3710M

How to use?

SM3710M

Pictures

SM3710M SM3710M SM3710M

1. temperature and current computing relationship

  The product comes standard with 0~50℃/-20~80℃/-40~60℃ multi-range. The default range is 0~50℃. Users can modify the range by dialing the switch. For example, the range is 0~50℃, the analog output is 4~20mA current signal, temperature and current The calculation relationship is as shown in the formula: C = (A2-A1) * (X-B1) / (B2-B1) + A1, where A2 is temperature range upper limit, A1 is the lower limit of the range, B2 is current output range upper limit, B1 is the lower limit, X is the currently read temperature value, and C is the calculated current value. The list of commonly used values is as follows:
current(mA)temperatureValue (℃) Calculation Process
40.0(50-0)*(4-4)÷(20-4)+0
53.1(50-0)*(5-4)÷(20-4)+0
66.3(50-0)*(6-4)÷(20-4)+0
79.4(50-0)*(7-4)÷(20-4)+0
812.5(50-0)*(8-4)÷(20-4)+0
915.6(50-0)*(9-4)÷(20-4)+0
1018.8(50-0)*(10-4)÷(20-4)+0
1121.9(50-0)*(11-4)÷(20-4)+0
1225.0(50-0)*(12-4)÷(20-4)+0
1328.1(50-0)*(13-4)÷(20-4)+0
1431.3(50-0)*(14-4)÷(20-4)+0
1534.4(50-0)*(15-4)÷(20-4)+0
1637.5(50-0)*(16-4)÷(20-4)+0
1740.6(50-0)*(17-4)÷(20-4)+0
1843.8(50-0)*(18-4)÷(20-4)+0
1946.9(50-0)*(19-4)÷(20-4)+0
2050.0(50-0)*(20-4)÷(20-4)+0
    As shown in the above formula, when measuring 8mA, current current is 16.5℃。

2. humidity and current computing relationship

  For example, the range is 0~100%RH, the analog output is 4~20mA current signal, humidity and current The calculation relationship is as shown in the formula: C = (A2-A1) * (X-B1) / (B2-B1) + A1, where A2 is humidity range upper limit, A1 is the lower limit of the range, B2 is current output range upper limit, B1 is the lower limit, X is the currently read humidity value, and C is the calculated current value. The list of commonly used values is as follows:
current(mA)humidityValue (%RH) Calculation Process
40.0(100-0)*(4-4)÷(20-4)+0
56.3(100-0)*(5-4)÷(20-4)+0
612.5(100-0)*(6-4)÷(20-4)+0
718.8(100-0)*(7-4)÷(20-4)+0
825.0(100-0)*(8-4)÷(20-4)+0
931.3(100-0)*(9-4)÷(20-4)+0
1037.5(100-0)*(10-4)÷(20-4)+0
1143.8(100-0)*(11-4)÷(20-4)+0
1250.0(100-0)*(12-4)÷(20-4)+0
1356.3(100-0)*(13-4)÷(20-4)+0
1462.5(100-0)*(14-4)÷(20-4)+0
1568.8(100-0)*(15-4)÷(20-4)+0
1675.0(100-0)*(16-4)÷(20-4)+0
1781.3(100-0)*(17-4)÷(20-4)+0
1887.5(100-0)*(18-4)÷(20-4)+0
1993.8(100-0)*(19-4)÷(20-4)+0
20100.0(100-0)*(20-4)÷(20-4)+0
    As shown in the above formula, when measuring 8mA, current current is 29%RH。