[SM7561M]  Magnetic illuminance sensing current output


SM7561M

Technical Parameters

Technical parameterParameter value
BrandSONBEST
Illuminance measuring range0~10 0000Lux
Illuminance allow deviation±7%
Repeatability test±5%
Illuminance detection chipImport digital
Wavelength range380nm~730nm
Communication InterfaceRS485
Default baud rate9600 8 n 1
PowerDC9~24V 1A
Running temperature-30~85℃
Working humidity5%RH~90%RH

Product Size

SM7561M

Wiring instructions

Why choose this product?

SM7561M SM7561M SM7561M SM7561M

How to use?

SM7561M

Application solution

SM7561M

Pictures

SM7561M SM7561M SM7561M SM7561M

Communication Protocol

    The product uses RS485 MODBUS-RTU standard protocol format, all operation or reply commands are hexadecimal data. The default device address is 1 when the device leaves the factory, and the module or NON-Recorder default baud rate is 9600,8,n,1 ,but data recorder default baud rate is 115200 .
1. Read data (function code 0x03)
    Inquiry frame (hexadecimal), sending example: query 1 data of 1# device, the upper computer sends the command: 01 03 00 00 00 01 84 0A .
Address Function Code Start Address Data Length Check Code
010300 0000 0184 0A
    For the correct query frame, the device will respond with data: 01 03 02 00 79 79 A6 , response format:
Address Function Code LengthData 1Check Code
0103 0200 79 79 A6
    Data description: The data in the command is hexadecimal, take data 1 as an example, 00 79 is converted to decimal value is 121, for general Sobo products, the temperature and humidity data magnification is 100, and the light data The magnification is 1 or 10. The data magnification of this product is 10, then the real value is: 121*10=1210, and so on.
2. Common data address table
Configuration Address Register Address Register Description Data Type Value Range
4000100 00IlluminanceRead Only0~65535
4010100 64Model CodeRead/Write0~65535
4010200 65 total number of measuring points read/write 1~20
4010300 66device addressread/write1~249
4010400 67baud rateread/write0~6
4010500 68communication moderead/write1~4