[SR2510B-5]  RS485 interface TFT color screen 5 channel SHT30 temperature and humidity recorder

SR2510B-5

Technical Parameters

Technical parameterParameter value
BrandSONBEST
Temperature measuring range-30℃~80℃
Temperature measuring accuracy±0.5℃ @25℃
Support sensorSHT30
Channels5
Input busIIC
Communication InterfaceRS485
Default baud rate9600 8 n 1
PowerDC6~24V 1A
Storage128M
Max Records500000
Running temperature-30~85℃

Product Size

SR2510B-5 SR2510B-5 SR2510B-5 SR2510B-5 SR2510B-5 SR2510B-5

Wiring instructions

Why choose this product?

SR2510B-5 SR2510B-5 SR2510B-5

How to use?

SR2510B-5

Application solution

SR2510B-5 SR2510B-5

Product List

SR2510B-5

Pictures

SR2510B-5 SR2510B-5

Communication Protocol

    The product uses RS485 MODBUS-RTU standard protocol format, all operation or reply commands are hexadecimal data. The default device address is 1 when the device leaves the factory, and the module or NON-Recorder default baud rate is 9600,8,n,1 ,but data recorder default baud rate is 115200 .
1. Read data (function code 0x03)
    Inquiry frame (hexadecimal), sending example: query 1 data of 1# device, the upper computer sends the command: 01 03 00 00 00 05 85 C9 .
Address Function Code Start Address Data Length Check Code
010300 0000 0585 C9
    For the correct query frame, the device will respond with data: 01 03 0A 00 79 00 00 00 00 00 00 00 00 2B 24 , response format:
Address Function Code LengthData 1Data 2Data 3Data 4Data 5Data 6
Data ...Data 9Data 10Check Code0103 0A00 7900 7A
00 7B00 7C00 7D00 7E............00 7900 79 2B 24
    Data description: The data in the command is hexadecimal, take data 1 as an example, 00 79 is converted to decimal value as 121, assuming the data magnification is 100, then the real value is 121/100=1.21, Others and so on.
2. Common data address table
Configuration Address Register Address Register Description Data Type Value Range
4000100 001#temperature registerRead Only0~65535
4000200 012#humidity registerRead Only0~65535
4000300 023#temperature registerRead Only0~65535
4000400 034#humidity registerRead Only0~65535
4000500 045#temperature registerRead Only0~65535
4000600 056#humidity registerRead Only0~65535
...............
4000900 089#temperature registerRead Only0~65535
4001000 0910#humidity registerRead Only0~65535
4010100 64Model CodeRead/Write0~65535
4010200 65 total number of measuring points read/write 1~20
4010300 66device addressread/write1~249
4010400 67baud rateread/write0~6
4010500 68communication moderead/write1~4
4010600 69protocol typeread/write1~10